EvvyTools.com EvvyTools.com
Home About Home & Real Estate Health & Fitness Freelance & Business Everyday Calculators Writing & Content Dev & Tech Cooking & Kitchen Personal Finance Math & Science Data Lists Subscribe Contact
Sign In Create Account

Electrical Power Calculator - Watts, kVA, Amps & More

Calculate watts, kVA, HP, motor starting, and amperage

Work with electrical power calculations across five modes — from basic wattage to generator sizing for motor starting. Whether you are sizing a panel, converting between kW and kVA, or figuring out amperage for a three-phase circuit, this calculator covers the essentials.

Pro tip: Power factor matters — a motor rated at 10 kVA with a 0.8 PF only delivers 8 kW of real power. Always account for power factor when sizing generators and breakers.

V
A
0.85
Formula Used
P = V × I × PF = 240 × 30 × 0.85 = 6,120 W
kW
PF
Formula Used
kVA = kW / PF = 10 / 0.80 = 12.50 kVA
HP
Formula Used
kW = HP × 0.7457 = 10 × 0.7457 = 7.457 kW
HP
Formula Used
Generator kVA = HP × 0.7457 / PF × Multiplier
kVA
V
Formula Used
I = kVA × 1000 / V = 10 × 1000 / 240 = 41.67 A
Power
6,120 W
Kilowatts
6.12 kW
Apparent Power
7.20 kVA
Power Factor
0.85
AWGMax AmpacityTypical Breaker
14 AWG15 A15 A
12 AWG20 A20 A
10 AWG30 A30 A
8 AWG40 A40 A
6 AWG55 A60 A
4 AWG70 A70 A
2 AWG95 A100 A
1/0 AWG125 A125 A
2/0 AWG145 A150 A
3/0 AWG165 A175 A
4/0 AWG195 A200 A

Add multiple loads to build a complete electrical load schedule for panel design.

Load NameWattsVoltagePhase
Load Schedule Builder requires subscription

Enter wire gauge, run length, and load to check voltage drop against NEC 3%/5% limits.

Voltage Drop Calculator requires subscription

Recommends breaker size based on load with 80% continuous load derating per NEC.

Breaker Sizing Guide requires subscription
Disclaimer: This tool provides general estimates for educational purposes. Consult a certified electrical professional for actual installations. Results require consideration of site-specific factors including motor efficiencies, altitude, derating, prime vs standby power, and local electrical codes.
Save requires subscription

How to Use the Electrical Power Calculator

This calculator offers five distinct modes accessible from the tabs at the top. In Power mode, enter voltage, current, and power factor to find real power in watts and kilowatts. Toggle between single-phase and three-phase to see how the formula changes. The kW/kVA and kW/HP converters handle bidirectional conversions with a single click. Use Motor Starting to size a generator for motor inrush current, and Amperage to find amps from kVA and voltage. Each mode displays the formula being used so you can verify or learn the math behind the result.

Understanding Power Factor

Power factor is the ratio of real power (watts) to apparent power (volt-amps). A purely resistive load like a heater has a power factor of 1.0 — all the power drawn is converted to useful work. Motors, transformers, and fluorescent lighting are inductive loads with power factors typically between 0.7 and 0.9, meaning some of the current drawn does no useful work but still flows through wiring and transformers. This matters because your wiring, breakers, and generator must be sized for apparent power (kVA), not just real power (kW). A 10 kW load at 0.8 power factor actually demands 12.5 kVA from your supply. Utilities may penalize commercial customers with low power factor, so capacitor banks are often installed to bring PF closer to unity.

Single Phase vs Three Phase

Single-phase power uses two wires (one hot, one neutral) and is standard in residential settings. In the United States, most homes receive split-phase 240V service, which is technically two 120V phases 180 degrees apart. Three-phase power uses three hot conductors with voltages 120 degrees apart and is the backbone of commercial and industrial electrical systems. The key advantage of three-phase is that it delivers more power with less copper — a three-phase system delivers 1.732 times the power of a single phase at the same voltage and current. That is where the square root of three (1.732) factor appears in three-phase formulas. Common three-phase voltages include 208V, 480V, and 600V. If you are connecting a motor or large piece of equipment, check the nameplate to determine whether it requires single-phase or three-phase supply.

Generator Sizing for Motors

Electric motors draw 5 to 7 times their rated running current during startup. This inrush current lasts only a few seconds but can stall or trip a generator that is too small. The starting method dramatically affects how much inrush the generator must handle. Direct On-Line (DOL) starting applies full voltage instantly and creates the highest inrush — roughly 7 times the motor kW in generator kVA. Star-Delta starters reduce inrush to about 2.5 times by starting the motor at reduced voltage. Soft starters ramp up voltage gradually and typically need about 1.8 times. VFDs (Variable Frequency Drives) control both voltage and frequency and only require about 1.5 times, making them the most generator-friendly option. Always confirm sizing with the generator manufacturer and account for other simultaneous loads.

Voltage Drop Basics

Every wire has resistance, and as current flows through it, some voltage is lost as heat. The NEC recommends no more than 3% voltage drop for branch circuits and 5% total for feeder plus branch circuits combined. Excessive voltage drop causes motors to run hot and inefficiently, lights to dim, and sensitive electronics to malfunction. Voltage drop increases with wire length and load current, and decreases with larger wire gauge. For long runs — such as feeding a detached garage or barn — you may need to upsize your wire significantly. The premium voltage drop calculator lets you verify your wire selection before you pull a single foot of cable.

Electrical Safety Considerations

Working with electricity is inherently dangerous and should only be performed by qualified individuals. Always de-energize circuits before working on them and verify with a meter that power is off. The NEC requires overcurrent protection (breakers or fuses) sized to protect the conductor, not the load. A 20-amp breaker protects 12 AWG wire from overheating, regardless of what is plugged into the circuit. For continuous loads — those expected to run for three hours or more — the NEC requires the breaker to be rated at 125% of the load, which effectively means the load cannot exceed 80% of the breaker rating. This derating is one of the most commonly overlooked requirements in residential work. When in doubt, consult a licensed electrician who understands your local codes and conditions.

Looking for related tools? Try our Electricity Cost Calculator to see how much power costs you, or our Unit Converter for general measurement conversions. Explore all Everyday Calculator tools.

Link copied to clipboard!